- Details
-
Published on Thursday, 06 June 2019 17:02
Limit Switch Sensors Circuits
The use of optical sensors to replace mechanical switches is an important feature of today's automation techniques. The mechanical switch is prone to failure after a relatively short operating life. Solid-state sensors have no moving parts to wear, jam, or stick and hence have much longer operating life.
Optical sensors are quiet and require no force to operate. They can be activated by a web of paper or a foil vane attached to a meter movement. No open mechanical contacts are involved. Mechanical contacts wear, pit, and stick. Even low current reed relays are known to stick at the most inopportune time.
Light in Motion offers two families of optical limit switches, a slotted family with tabs H21BX, Figure 1, and a slotted family without tabs, H22BX, Figure 2. Both types employ a photodarlington as the detector and an infrared LED as the light source. The detector sees the infrared light and provides a collector current proportional to the brightness of the light incident on the detector, Figure 3. There are 3 ranges of sensitivity, B1, B2 and B3 in increasing order. In the following developments we will use the
H21B1.
Figure 1. H21BX Slotted object Sensor Figure 2. H22BX Slotted object Sensor with tabs without tabs Figure 3. H21B1 Circuit SchematicsThe electronic circuits used with the optical sensors must be properly designed to match the performance of the photodarlington circuit in the detector. The detector is capable of saturating at I
C = 2mA with normal LED drive currents (see data sheets). The load resistance must match this current capability. A typical connection of the H21B1 is shown in Figure 4, and the transfer function of the circuit is shown on the graph of Figure 5. Note that for load resistances above 10K ohm the detector is very sensitive and will function well only with a value of I
F less than 5mA or with a completely opaque interrupting vane.
Figure 4. Typical H21B1 Circuit Connection Figure 5. Transfer Function Load Plot for H21B1Since the H21B1 can easily sink I
C = 2mA at V
C = 0.7V it can be connected directly to the input of TTL logic as shown in Figure 6.However since the frequency response is quite slow compared to TTL switching requirements, it is recommended that the H21B1 be first connected to a Schmitt trigger, as shown, to improve rise and fall times. A frequency response of 1KHz is adequate for most mechanical motion detection.
Figure 6. Current Sink for Driving a TTL Schmitt TriggerA typical 3-wire circuit for using the H21B1 is shown in Figure 7. The value of resistor R
D determines I
F, and R
L determines the load line and sensitivity.
Figure 7. 3-Wire Circuit for H21B1 The circuit of Figure 8 illustrates one method of obtaining 2-wire sensing since the R
L and eo terminal can be remote from the sensor. With a V
cc = 20V, R
L = R
D = 1K and a current transfer ratio or 100%, a signal delta of 2V is obtained at e
0 when the LED light is interrupted.
Figure 8. 2-Wire Circuit for H21B1 A more complicated circuit is shown in Figure 9 where a current booster amplifier is used to shunt the photodarlington sensor. A Zener diode is included to maintain IF when the light is interrupted. Again, 2-wire remote sensing is possible and a signal of ̴ V
z is obtained. Other variations are possible.
Figure 9. Improved 2-Wire H21B1 circuit The current booster circuit of Figure 9 can be used in a complete all solid-state intrusion alarm circuit as shown in Figure 10. In the intrusion detector loop a series of SCR opto-isolators is installed across each of the sensor segments shown as tapes or switches. So long as the tapes or switches are closed circuits the corresponding LED is not energized by the constant current supply. If any of the tapes or switches are opened, the corresponding SCR is triggered via the LED and sets off an alarm indicator. If the circuit is opened, an excess voltage alarm is triggered, and a current presence alarm also sounds. The H21B1 and its booster keeps the voltage across its LED below threshold so long as the light is not interrupted. If the light is interrupted for only a moment the SCR is triggered. The vane for the H21B1 slot could be always in place with a hole to allow the light through. If the vane is moved, or removed from the slot, the light is interrupted. In this method the H21B1 can replace all mechanical door switches, magnetic window switches, etc. where a small movement will trigger the alarm system.
Figure 10. Intrusion Alarm Detector Circuit
Download PDF